Technical data
Operation with rated power (normal operation)
Rated data for 480 V mains voltage
3
139
EDKVF9333V DE/EN/FR 7.2
3.3.2 Rated data for 480 V mains voltage
Basis of the data
Voltage Frequency
AC mains connection [U
N
] 3/PE AC 384 V − 0 % ... 528 V + 0 % 45 Hz − 0 % ... 65 Hz + 0 %
DC−mains connection
(alternatively)
[U
DC
] DC 540 V − 0 % ... 740 V + 0 % ˘
Output voltage
With mains choke 3 ~ 0 approx. 94 % V
rated
˘
Without mains choke 3 ~ 0 ... U
N
˘
9300 Mains current
1)
Typical motor power Output power Power loss
With
Mains choke
Without
Mains choke
ASM
(4−pole)
2/4 kHz
2)
8 kHz
2)
U, V, W U, V, W +U
G
, −U
G
3)
Type I
r
[A] I
r
[A] P
rated
[kW] P
rated
[hp] S
rated
[kVA] S
rated
[kVA] P
DC
[kW] P
loss
[W]
EVF9321−xV 1.5 2.1 0.37 0.5 1.2 1.2 2.3 50
EVF9322−xV 2.5 3.5 0.75 1.0 2.1 2.1 0.9 65
EVF9323−xV 3.9 5.5 1.5 2.0 3.2 3.2 0 100
EVF9324−xV 7.0 ˘ 3.0 4.0 5.8 5.8 2.5 150
EVF9325−xV 12.0 16.8 5.5 7.5 10.8 10.8 0 210
EVF9326−xV 20.5 ˘ 11.0 15.0 18.5 18.5 0 390
EVF9327−xV 29.0 43.5 18.5 25.0 26.6 26.6 11.8 430
EVF9328−xV 42.0 ˘ 30.0 40.0 39.1 39.1 4.6 640
EVF9329−xV 55.0 ˘ 37.0 50.0 49.9 49.9 0 810
EVF9330−xV 80.0 ˘ 55.0 75.0 69.8 69.8 5.9 1100
EVF9331−xV 100 ˘ 75.0 100 91.4 91.4 0 1470
EVF9332−xV 135 ˘ 90.0 125 124 124 32.4 1960
EVF9333−xV 165 ˘ 110.0 150 158.2 149 47.1 2400
1)
Mains currents at a switching frequency of 8 kHz
2)
Switching frequency of the inverter
3)
Power supplied by the DC bus when operating with power−adapted motor
˘ Operation allowed only with mains choke or mains filter