EasyManua.ls Logo

Lenze 9300 vector Series - Wiring of the System Bus (CAN)

Lenze 9300 vector Series
330 pages
Go to English
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical installation
Wiring of the system bus (CAN)
5
211
EDKVF9333V DE/EN/FR 7.2
5.9 Wiring of the system bus (CAN)
Installation material required from the scope of supply:
Description Use Quantity
Terminal strip, 3−pole Connection of system bus (CAN) at X4 1
Wiring
A
1
A
2
A
3
A
n
93XX 93XX 93XX
GND GND GND GNDLO LO LO LOHI HI HI HIX4 X4 X4PE PE PE PE
120 120
9300VEC054
Fig. 5−30 System bus (CAN) wiring
A
1
Bus device 1 (controller)
A
2
Bus device 2 (controller)
A
3
Bus device 3 (controller)
A
n
Bus device n (e. g. PLC), n = max. 63
X4/GND CAN−GND: System bus reference potential
X4/LO CAN−LOW: System bus LOW (data line)
X4/HI CAN−HIGH: System bus HIGH (data line)
Stop!
Connect a 120 W terminating resistor to the first and last bus device.
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type Paired with shielding
Impedance 120 W (95 ... 140 W)
Cable resistance/cross−section
Cable length £ 300 m £ 70 mW/m / 0.25  0.34 mm
2
(AWG22)
Cable length 301  1000 m £ 40 mW/m / 0.5 mm
2
(AWG20)
Signal propagation delay £ 5 ns/m