Electrical installation
Installation according to EMC (installation of a CE−typical drive system)
5
165
EDKVF9333V DE/EN/FR 7.2
Control cables
ƒ For lengths of 200 mm and more, use only shielded cables for analog and digital
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.
ƒ Connect the shield correctly:
The shield connections of the control cables must be at a distance of at least
50 mm from the shield connections of the motor cables and DC cables.
For cables for digital inputs and outputs, connect the shield at both ends.
For cables for analog inputs and outputs, only connect the shield at the drive
controller end.