Electrical installation
Control terminals
Device variant with "Safe torque off" function
5
208
EDKVF9333V DE/EN/FR 7.2
Supply via internal voltage source
ƒ If a freely assignable digital output (e.g. X5/A1) is assigned permanently to HIGH
level, it serves as an internal voltage source. Every output has a maximum load
capacity of 50 mA.
– The relay K
SR
and two digital inputs (X5/28 and e.g. X5/E1) can be supplied with
voltage via a digital output.
– Two digital outputs must be connected in parallel and assigned permanently to
HIGH level in order to obtain the maximum wiring (relays K
SR
and X5/E1 ... X5/E5,
X5/ST1).
ƒ For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.
GND2 +24V+5 V
DIGOUT4
E5
A2 A3 A4 ST1
ST2
59
39
3k
47k
50mA
50mA
50mA
50mA
X5
28
E1 E2 E3 E4
3k
3k
3k
3k
3k
X11
K31K32 33 34
S1 S2
IN1 IN2
IN3
IN4
+
K
SR
A1
Z1
X3
GND1 GND1
X6
12
3
4
7762
63
242R
1
2
3
4
5
6
100k
100k
100k
100k
3.3nF
AIN1 AIN2
AOUTx
AOUT2
AOUT1
1
3
247
10k 10k
9300vec135
Fig. 5−28 Wiring of digital and analog inputs/outputs with active "Safe torque off" function and internal
voltage source
S1 Deactivate pulse inhibit (1st disconnecting path)
S2 Enable controller (2nd disconnecting path)
Z1 Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function
X5/A4 Feedback via a digital output (e. g. DIGOUT4)
NO contact or NC contact
Z
Load
Minimum wiring required for operation
Terminal assignment in the Lenze setting: 210