Leviton D4200 LCD Ver 2.0 Architectural Lighting Controller Page 11 of 80
If a remote DC power supply is used and you have
multiple Luma-Net runs, all DC common wires must be
joined at the power supply.
At the last control station or dimmer cabinet on both
ends of the run, a small jumper wire must be run from
the terminal labeled “Rem-” to the terminal marked
“Term” on that last station. This jumper wire properly
terminates the digital communications lines at the end of
the line. See Figure 6.
Wiring the Phoenix Connector
Step 1: Connect leads per wiring diagram as illustrated in Figure 4.
Step 2: Twist strands of each lead tightly (making sure that there
are no stray strands) and push firmly into appropriate plug
connector location.
Step 3: Tighten the screws on the plug connector—making sure
that no bare conductor is showing.
Step 4: Tie the Drain/Shield wires together and insulate using a
small piece of heat shrink tubing.
Step 5: Install termination jumpers as required. Remember a
termination jumper is required at the two ends of the
Luma-Net run.