User Guide
Leviton D4200 LCD Ver 2.0 Architectural Lighting Controller Page 25 of 80
To exit the Programming and Configuration Level menu:
Step 1: Press and hold the Menu/Cancel button for 10 seconds,
until LEVITON appears on the LCD display.
Step 2: Wait until the LCD display changes to MANUAL MODE.
Operate the buttons on the D4200 one at a time.
Pressing two or more buttons at once may not yield the
desired result.
Setting the Network ID - MANDATORY
Each control station must have a unique ID number assigned to it. A
Net ID of Zero (0) prevents the station from participating on the
network.
These numbers may have been assigned at the factory
prior to shipment. When assigned at the factory each
station is labeled with its ID number.
The network ID must be set to a unique number between 001 and
127. If two stations have the same network ID, all stations may
operate erratically and the dimmers will not respond to any station.
Default Settings
The default network ID is set to 000. When the station is reset or
powered on and the network ID is zero, the LCD will prompt you for a
valid network ID.
All eight personalities have their “Remote To” IDs set to 0. By default,
when a “Remote To” IDs set to 0, it is as if it set to the same as the
network ID.