Table 31: Properties of the Analog Input object providing feedback from DALI ballasts, groups, and
channels.
Object_Identifier (Read-Only)
The instance number is equal to the instance number of the corresponding Analog Output
object (see Section 8.3.3.10).
Object_Name (Read-Only)
This property holds the value of the Object_Name of the associated Analog Output object
with the addition “Feedback”.
Object_Type (Read-Only)
The value of this property is ANALOG_INPUT (0).
Present_Value (Read-Only)
This property, of type REAL, indicates the linearized percentage (0..100.00%) of the DALI
device’s, group’s or channel’s current light output.
Device_Type (Read-Only)
This property contains the value “Actual Dim Level”.
Status_Flags (Read-Only)
Of the four flags the flags IN_ALARM, FAULT, and OUT_OF_SERVICE are linked to the
state of the corresponding properties Event_State, Reliability and Out_Of_Service as
described by the standard.
OVERRIDDEN Always FALSE.
Reliability (Read-Only)
The Reliability property for this object type may have any of the following values: