L-DALI User Manual 56 LOYTEC
Version 5.2 LOYTEC electronics GmbH
5 Web Interface
L-DALI models with an Ethernet interface come with a built-in Web server and a Web
interface to configure the device and extract statistics information. The Web interface
allows configuring the IP settings, CEA-852 and CEA-709 settings, BACnet settings and
managing the DALI devices. This interface is very simple to use and has an intuitive, self-
explanatory user interface.
5.1 Device Information and Account Management
In a Web browser enter the default IP address 192.168.1.254 of the L-DALI. Note that if
your PC has an IP address in a subnet other than 192.168.1.xxx you must open a command
tool and enter the following route command to add a route to the L-DALI:
To Add a Route to the Device
1. Windows START Run
2. Enter ‘cmd’ and click Ok.
3. In the command window enter the command line
route add 192.168.1.254 %COMPUTERNAME%
4. Then open your Web browser and type in the default IP address 192.168.1.254.
5. The device information page should appear as shown in Figure 43.