EasyManua.ls Logo

LOYTEC L-DALI - Page 337

LOYTEC L-DALI
393 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
L-DALI User Manual 337 LOYTEC
Version 5.2 LOYTEC electronics GmbH
Device_Type (Read-Only)
This property contains the type of DALI sensor (e.g. “Tridonic Sensor”).
Status_Flags (Read-Only)
Of the four flags the flags IN_ALARM, FAULT, and OUT_OF_SERVICE are linked to the
state of the corresponding properties Event_State, Reliability and Out_Of_Service as
described by the standard.
OVERRIDDEN Always FALSE.
Reliability (Read-Only)
The Reliability property for this object type may have any of the following values:
NO_FAULT_DETECTED No fault was detected.
NO_SENSOR No sensor assigned or some failure reported by the
DALI sensor (no light value reported).
COMMUNICATION_FAILURE Sensor offline.
UNRELIABLE_OTHER Other failure detected.
Units (Read-Only)
The value of this property is 37 (lux).
Min_Pres_Value (Read-Only)
The value of this property is 0.
Max_Pres_Value (Read-Only)
The value of this property is “Infinity”.
Profile_Name (Read-only)
The value of this property is 178-http://www.loytec.com/xsd/DALILightSensor/v1”.
Lux_2 (Read-only)
If the assigned sensor provides multiple lux level sensor values this property (property ID
557) reports the current second light level value reported by the sensor. No gain table
correction is applied.
Intrinsic reporting
The object supports all properties required for intrinsic reporting. Per default only fault
alarms are enabled.
8.3.4.3 Binary Input Object DALI occupancy sensor
This object is used to represent the occupancy sensor part of a DALI Sensor (see Table 37).
There is a maximum of 16 such objects per channel.

Table of Contents