EasyManua.ls Logo

Meggitt VM600 - Page 238

Meggitt VM600
362 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9 - 34 VM600 MPS hardware manual (standard version) MAMPS-HW/E
Edition 17 - February 2018
Configuring the four local relays on the IOC4T
CONFIGURATION OF MPC4 / IOC4T CARDS
Configuration examples for relay RL1 using a a control signal with a normal state of 1
(see Table 9-4):
a. To configure RL1 to act as a normally energised (NE) relay with normally closed
(NC) contacts (see Table 9-5):
Jumper J1005 has contacts 1-3 closed.
Jumper J703 has contacts 1-2 closed.
In this case, RL1 provides a closed circuit when there is no alarm. It provides an
open circuit in the event of an alarm or power supply failure.
b. To configure RL1 to act as a normally de-energised (NDE) relay with normally closed
(NC) contacts (see Table 9-5):
Jumper J1005 has contacts 1-2 closed.
Jumper J703 has contacts 1-3 closed.
In this case, RL1 provides a closed circuit when there is no alarm or when there is a
power supply failure. It provides an open circuit in the event of an alarm.
Figure 9-24: Position of jumpers used to configure the IOC4T local relays as NE or NDE
Connector
J2
(Top of card)
(Bottom of card)
Note: The J100x and J70x
jumper settings depend on the
normal state of the control
signal (see Table 9-4) and the
required operation of the relay
(see Table 9-5).

Table of Contents

Other manuals for Meggitt VM600

Related product manuals