82. Function of Function data
D F01 Selection of decimal point at display position
Initial value00000 00000Non
0000110
1
0000210
2
0000310
3
0000410
4
D F03 Selection of display rate
Initial value00000 000004 times/s
0000120 times/s
D F04 Setting digital filter
Initial value00003 Setting range:=0000000008, Average of 2
(n)
times
Select the average times for digital filter. When the figure grows larger, the filter will
become stronger, then effects from vibrations and so on are shown scarcely on the
display. However, if too large figure is selected, the response to variation of input
sensor will become worse.
Using the digital filter where vibrations and so on may exist is effective for removing
the deflection on the display.
D F06 Setting key lock
Initial value00000 10
0
digit ON/OFF of CHECK value(Press the key in the
condition of pressing
key.)
10
1
digit ON/OFF of Peak Hold function, A/Z ON(),
Reset of the peak value, A/Z OFF(
)
10
2
digit Reading out the change mode of S1 setting(),
Reading out the change mode of S2 setting(
)
10
3
digit Execute the zero setting(Press the key
in the condition of pressing the
key.)
10
4
digit Reading out the function mode()
The setting of “0” makes the lock OFF of key function, and the setting of “1” makes
the lock ON of key function. Moreover, when the reading out the function mode is
locked, the function mode can be proceeded after pressing the
key for over 2
seconds in the condition of pressing the
key for over 1 second.
D F08 Setting zero tracking data width
Initial value00000 00000Zero tracking OFF
Setting range0000000099
Unit0.5D
Data width of 49.5D with the setting “00099”.
Effective only when the value of 0000100099 is set with the F07.