120
• Job Info
o Shows details of the job's name, number, creation date and author. The
multi-line comments field can be edited and become part of the job's version
history.
• Options
o Two Stage - check to enable two stage. As per UL 864 and UL 2572 only a
setting of Single Stage (disabled) is permissible.
o Fire Drill - check to enable the panel's Fire Drill switch.
o Manual Signal Silence- check to enable the panel's Signal Silence switch.
o Style D (Class A) Conv Inputs - check this box to indicate that the panel has
Class A (formerly Style D) conventional inputs.
o Style D (Class A) Input Modules - check this box to indicate that input
modules' field wiring is Class A (formerly Style D).
o Style 6 and 7 (Class A) Loop - check this box to indicate that the panel has
Class A or Class X (formerly Style 6 and 7) addressable loop(s).
o Style Z (Class A) Fire Phone - check this box to indicate that the wiring from
an addressable fire phone module and the handset is Class A (formerly Style
Z).
o Style 7 (Class A) Network - check this box to indicate that the wiring between
Network Nodes is Class X (formerly Style 7).
o Digital Audio - check this box to indicate that the audio signals use the
Arcnet wiring between Network Nodes. If not checked, then the audio runs
over a separate pair of wires.
o Digital Phone - check this box to indicate that the Fire Phones use the Arcnet
wiring between Network Nodes. If not checked, then the phone
conversations use a separate pair of wires.
o Single Bypass Trouble - Setting this option will suppress troubles for ALL
bypassed output ckts. Only the Signal Bypass switch active trouble will be
generated by Bypassing from a switch on a DSPL or IPS-2424.
o Monitor Alert- When set, all monitor should activate the buzzer as a
supervisory, otherwise the buzzer will stay silent.