121
o Silence NAC Audibles Only - If both flags "Silence NAC Audibles Only" and
NS are checked the signal silence will silence the horn but the strobe will
continue to flash.
o Disable Waterflow Retard - this flag indicates there is no extra delay on
validating water-flow input activation.
o Subsequent Alarms: Only In Separate Zones. Unchecked Upon activation of a
subsequent alarm for any device in any zone the signals will re-sound.
Checked Upon activation of a subsequent alarm for only a device in a
different zone the signals will re-sound.
o Second stage alarm relay - Sets alarm relay to operate only when the 2nd
alarm stage is reached on a Two Stage system. Disabled unless Two Stage
checked. As per UL 864 and UL 2572 only a setting of Disabled is permissible.
o Relays follow node alarm - Sets Alarm relay to activate on node level alarm -
else system level alarm. Mutually exclusive with Second stage alarm relay.
o Relays follow node supv - Sets Supervisory relay to activate on node level
supervisory - else system level supervisory.
o Relays follow node trbl - Sets Trouble relay to activate on node level trouble
- else system level trouble.
o Drift Compensation - Enable drift compensation on photo detector. As per
UL864 and UL 2572 only a setting of Enable is permissible.
o Device LEDS flash when polled - check this box to indicate that the LEDs of
the addressable devices on the Base IO's loop flash when polled.
o Alarm transmit silence causes the PR-300 City Tie module to stop
transmitting the Alarm signal when Signal Silence is active.
o Disable Auto Test - check this box to disable the automatic testing of System
Sensor addressable devices.
o Automatic All Call - check this box to enable automatic "ALL-CALL" when PTT
or Digital message SW is pressed.
o Enable Page Switch with Evac Annun. - this check box will enable Amplifier
Evac/Alert Channel LED annunciation via the correlated Page Select Switch.
o Automatic Page To Evac - check this box to enable automatic "Page To Evac".