158
**-**-**-ST-002
Common
Trouble
Set to TRUE when any of this job's NODEs have
their "Node Trouble" status equal to TRUE.
**-**-**-ST-003
Common
Monitor
Set to TRUE when any of this job's NODEs have
their "Node Monitor" status equal to TRUE.
**-**-**-ST-004 Sys Reset
Set to TRUE while any of the Job's nodes have their
"Node Sys Reset Activ" status set to TRUE.
**-**-**-ST-005
SysReset
Inactive
The inverse of Sys Reset.
**-**-**-ST-006 Fire Drill
Set to TRUE when the Fire Drill operation has been
initiated. Remains TRUE until the Fire Drill switch is
pressed again or until a real fire alarm or
supervisory input is activated.
**-**-**-ST-007 Alarm Ack
The Alarm Ack status is set to TRUE to indicate that
the auto GA timer has been cancelled by the alarm
acknowledge or common signal silence common
controls. It is applicable only a 2 stage system.
**-**-**-ST-008 Alert Active
On two stage systems the Alert Active status is set
to TRUE to indicate that a first stage alarm has been
initiated as a result of the activation of an input
zone or zone activation switch configured for alarm
at an alert state.
Once the status is set it will stay active until system
reset.
**-**-**-ST-009 Evac Active
Set to TRUE when the "Node Evac Active" status is
TRUE on any of the job's Nodes.
**-**-**-ST-010
Alarm
Set to TRUE when "Node Subsequent Alarm" status
is TRUE on any of the job's Nodes.