159
**-**-**-ST-011
Total
Evacuation
The Total Evacuation alarm status is set to TRUE to
indicate that the total general alarm common
control has been activated or the auto GA timer has
timed out.
Once the status is set it will stay active until system
reset.
**-**-**-ST-012
Signal
Silence
Set to TRUE if Signal Silence has been pressed AND
there are outputs which are currently silenced
**-**-**-ST-013
Sig Silence
Pulse
This status will be TRUE for 4 seconds after the
Signal Silence switch is pressed.
**-**-**-ST-014
Sig Sil
Inhibit
This status is TRUE when signals cannot be silenced.
This is the case from the time when an alarm or
active supervisory input has been detected or
General Alarm has been activated until the signal
silence inhibit timer expires.
**-**-**-ST-015 Aux Disc
This status is set to TRUE when the common
auxiliary relays are bypassed (via the front panel
Bypass menu).
**-**-**-ST-016
Aux Reset
Pulse
This status is set to TRUE when the Aux Reset
button is pressed and remains on for 4 seconds
**-**-**-ST-017
New Alarm
Active
Set to TRUE when a first alarm occurs, when a
subsequent alarm occurs, when the GA timer
expires, when the GA switch is pressed or when a
zone switch configured as alarm is pressed.
The status remains TRUE until system reset. System
Reset is inhibited until the Signal Silence Inhibit
timer expires.
**-**-**-ST-018
Signals
Active
Set to TRUE when audible signals are active on any
of the job's Nodes.