160
**-**-**-ST-019
Silence
Opts Active
Set to TRUE when silenceable signals are active on
any of the job's Nodes.
**-**-**-ST-020
Auto GA
Timing
Set to TRUE when the Auto GA Timer is running.
If the system is configured as two stage and the
Auto G.A. timer is enabled, it is started when the
common alarm sequence is
the first alarm condition. It is cancelled if either
alarm acknowledge or common signal silence is
activated before it times out. A subsequent alarm
after the timer has been acknowledged restarts the
timer to its full period.
**-**-**-ST-021
Auto SS
Timing
Set to TRUE when the Signal Silence Timer is
running.
The Signal Silence inhibit timer is started when the
common alarm sequence is activated in response to
the first alarm condition. While the timer is running,
signal silence, zoned signal silence, system reset,
and paging operations are inhibited, and the signal
silence inhibited status is active.
**-**-**-ST-022
Auto Suite
Resound
This status becomes TRUE when the Auto Resound
timer expires.
The Auto Resound timer specifies the time, in
minutes, after which the signals will resound if an
alarm remains un-acknowledged. The configurable
range is from 5 to 12 minutes with a default of 10
minutes.
**-**-**-ST-023
Page
Inhibit
This status is set to TRUE when the page inhibit
timer is running.
The timer is started by the first active alarm.
**-**-**-ST-024
Alarm Xmit
Active
This status is set to TRUE when the common alarm
is active, but not if Aux Disc is active. NOTE: When
this is TRUE a signal will be sent to the UDACT/PR-
300 (thru a relay)