161
025
**-**-**-ST-025
Trouble
Xmit Active
This status is set to TRUE if "Node Trbl Xmit Activ" is
true on any of the job's Nodes.
026
**-**-**-ST-026 All Call This status is set to TRUE when All Call is active.
027
**-**-**-ST-027
Page to
Evac
This status is set to TRUE when Page to Evac is
active.
028
**-**-**-ST-028
Page to
Alert
This status is set to TRUE when Page to Alert is
active
029
**-**-**-ST-029
Page by
Phone
This status is set to TRUE when Page by Phone is
active.
030
**-**-**-ST-030
All Call
Minus
This status is set to TRUE when All Call Minus is
active.
031
**-**-**-ST-031
Pre-Tone
Active
Set to TRUE if the Pre-Tone is active on any of the
job's nodes.
032
**-**-**-ST-032 Page Ready
Set to TRUE when Page Ready is TRUE on all of the
job's nodes.
033
**-**-**-ST-033
Telephone
Call in
Set to TRUE when any fire phone goes off hook.
035
**-**-**-ST-035 Alm Buzzer
This status is set to TRUE if the conditions which
would cause the buzzer to sound at the alarm rate
are true.
036
**-**-**-ST-036
Supv
Buzzer
This status is set to TRUE if the conditions which
would cause the buzzer to sound at the supervisory
rate are true.