165
Node
Subsequent
Alarm
Set to TRUE when any of this NODE's CPUs have their "CPU Subseq
Alarm" status equal to TRUE.
Node Alarm
Verif
Set to TRUE when any of this NODE's CPUs have their "Alarm Verif"
status equal to TRUE.
Node Wflw
Retard
Set to TRUE when any of this NODE's CPUs have their "Wflw
Retard" status equal to TRUE.
Node Pre-
alarm
Set to TRUE when any of this NODE's CPUs have their "Pre-alarm"
status equal to TRUE.
Node Maint.
Alert
Set to TRUE when any of this NODE's CPUs have their "Maint. Alert"
status equal to TRUE.
Node Signals
Active
Set to TRUE when any of this NODE's CPUs have their "CPU Signals
Active" status equal to TRUE.
Node Signal
Silence
Set to TRUE when any of this NODE's CPUs have their "CPU Sig Sil
Active" status equal to TRUE.
Node Ground
Fault
Set to TRUE when any of this NODE's CPUs have their "Pos Ground
Fault" or "Neg Ground Fault" status equal to TRUE.
Node Trbl
Xmit Activ
Set to TRUE w
hen any of this NODE's CPUs have their "CPU Trouble
Xmit" status equal to TRUE.
Node Relay
Auto Test
Set to TRUE when any of this NODE's CPUs have their "Relay Auto
Test Active" status equal to TRUE.
Node Call
Control
This status is TRUE when the Call Control switch on a Master
Telephone display adder on this Node is depressed. This status is
typically correlated to a Telephone Selector switches LED and is
used to manage calls from one master phone to another.