166
020
Node Tel Call
In
This status is TRUE when telephone is off hook, or when a user at a
Master Telephone presses Call Control.
021
Alm Relay
Active
Set to TRUE when the alarm relay on this node is active. The alarm
relay is active when there is an alarm on any of this node's
connected CPUs.
022
Spv Relay
Active
Set to TRUE when the supervisory relay on this node is active. The
supervisory relay is active when there is an active supervisory on
any of this node's connected CPUs.
023
Trb Relay
Active
Set to TRUE when the supervisory relay on this node is active. The
supervisory relay is active when there is an active supervisory on
any of this node's connected CPUs.
024
Node PTT
Pressed
Set to TRUE of the PTT (Press To Talk) button is depressed on the
master telephone of this node.
025
Page Ready Set to TRUE if the Audio Controller on this node is ready to page.
026
Pre-Tone
Active
Set to TRUE when the pre-tone is playing on the Audio Controller
on this node.
027
Microphone
Trouble
Set to TRUE if any of the microphones on this node are in trouble.
028
Node Amp
Trouble
Set to TRUE if any of the amplifiers on this node have a trouble
condition.
031
Pretone Active
Set to TRUE pre-tone is sounding on this node.
032
Latched Relays
Set to TRUE if there are relays on this node that are latched and
awaiting a system reset or auxiliary reset.
033
Running a
Walktest
Walktest in progress on this node.