168
CPU Evac
Active
Set to TRUE when any input zone of process typ
e Alarm on this
CPU has reached the evac state. This status will
propagate to Node
Evac Active and from there to the job wide Common Evac Active
status.
CPU Subseq
Alarm
Set to TRUE when the second input zone on this CPU reaches the
Alarm state. The "Subsequent Alarm" common system status, which
was used before Suite Silence was officially supported, should not
be correlated to suite signals. See the Help Topic on Suite Silence.
Alarm Verif
Set to TRUE when an input of type "Verified Alarm" is in the process
of being verified.
Wlfw Retard
Set to TRUE from the time when waterflow is detected on an Input
Module of type Waterflow on this CPU until expiry of the retard
timer.
Note that this does not apply to sensors with their own built in
only applies to waterflow detection sensors
where the retard mechanism is managed by panel firmware.
Pre-alarm
Set to TRUE when any input device on this CPU that is not bypassed
has reached the pre
-alarm threshold. The status is set back to
FALSE if all inputs advance to the Evac or
Alarm state.
Maint. Alert
Set to TRUE when any input device on this CPU that is not bypassed
is detected to be dirty.
Pos Ground
Fault
Set to TRUE when the ground fault detection circuitry detects a
positive ground fault on this CPU.
Neg Ground
Fault
Set to TRUE when the ground fault detection circuitry detects a
negative ground fault on this CPU.
Note: This is only detected on the main board.
Remote
Trouble
This is a status coming from the UDACT to indicate there is a
problem with the
phone line or the UDACT is defective. Note: This
is only detected on the main board.