169
16
Battery
Trouble
Set to TRUE when the battery monitoring circuitry detects a trouble
with batteries on this CPU.
17
Power Fail
Set to TRUE when AC power has been lost
on this CPU.
Note: This is only detected on the main board.
18
CPU Trouble
Xmit
Set to TRUE if there is any trouble on this CPU. An
exception is
made for power fail. If power fail is the only trouble and the Power
Send Delay Timer has not yet expired, Tr
ouble Xmit remains FALSE.
19
CPU Latched
Opt
This status is set to TRUE if any relay on this CPU remains active
after the trigger input de
-activates or is reset. This can be the case
if a relay is configured to be latched until a System Reset or
Auxiliary
Reset. If a relay is correlated to the CPU Latched Opt
status its state is re
-evaluated.
20
CPU Signals
Active
Set to TRUE when audible signals are active on this CPU.
21
CPU Sig Sil
Active
This status indicates that there are outputs on this CPU that can be
silenceable and it will be set to FALSE when the SignalSilence switch
is pressed.
22
Relay Auto
Test Active
Not in use.
23
Control
Enabled
This status is TRUE if
1) If the local manual enable switch is activated: control is
unconditionally enabled
2) If a manual enable switch is activated at a control point "linked"
to this control point it is unconditionally enabled
3) Otherwise if a lockout time is running on another node in the
sam
e control group, control is disabled (unless the two displays
are
linked)
4) If this is a backup control point, control is only enabled if
communication to all the primary control points in the same control
group is down.
This may not yet be implemented. It is related to Display Linking
and Grouping.