148
: Self-diagnostics is performed. ×: Self-diagnostics is not performed.
(To the next page)
Diagnostics
Error
message
Diagnostic timing
CPU
module
status
LED status
L02CPU
L26CPU
-BT
RUN ERR.
Handling
error
Module verification
UNIT BAD
CONNECT
Execution of the END
instruction
Stop Off/On
Flashing/
On
Intelligent function module
assignment error
SP.UNIT LAY
ERR.
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
Intelligent module program
execution error
*1
SP.UNIT ERROR
Execution of the FROM/TO
instructions
Stop/
Continue
Off/On
Flashing/
On
Intelligent function module
version error
SP.UNIT
VER.ERR
Power-on/reset Stop Off Flashing
END cover is not attached NO END COVER
Power-on/reset
Execution of the END
instruction
Stop Off Flashing
Execution of the END
instruction
SYSTEM LAY
ERR
Power-on/reset Stop Off Flashing
No parameter MISSING PARA.
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
Boot error BOOT ERROR Power-on/reset Stop Off Flashing
Backup error
RESTORE
ERROR
Power-on/reset Stop Off Flashing
Memory card operation
error
*1
ICM.OPE.
ERROR
Insertion/removal of the
memory card
Stop/
Continue
Off/On
Flashing/
On
××
File setting error
FILE SET
ERROR
Power-on/reset
Writing to programmable
controller
Stop Off Flashing
File access error
*1
FILE OPE.
ERROR
Instruction execution
Stop/
Continue
Off/On
Flashing/
On
Instruction execution
disabled
CAN'T EXE.PRG.
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
Parameter
error
Parameter setting check
PARAMETER
ERROR
Power-on/reset
Switching from STOP to RUN
Writing to programmable
controller
Stop Off Flashing
SFC parameter error
SFC
PARA.ERROR
Switching from STOP to RUN
Writing to programmable
controller
Stop Off Flashing
Intelligent function module
parameter error
SP.PARA.
ERROR
Power-on/reset Stop Off Flashing
Password error
REMOTE
PASS.ERR
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
Instruction code check
INSTRUCT.
CODE ERR
Power-on/reset
Switching from STOP to RUN
Instruction execution
Stop Off Flashing
No END instruction
MISSING END
INS.
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
Pointer setting error
CAN'T SET(P)
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing
CAN'T SET(I)
Power-on/reset
Switching from STOP to RUN
Stop Off Flashing

Table of Contents