Serial interface (Modbus)
10/05 AWB8230-1541GB
182
150F A220 Frequency reference input –
reference value through
keypad, PNU A001 must
equal 02 (second parameter
set)
rw 0–400Hz 0.1 [Hz]
1510 A241 Boost function (second
parameter set)
DF51 only
rw 00: Manual 00
01: Automatic
1511 A242 Boost, manual voltage
boost (second parameter
set)
rw 0 – 20 % 0.1 [%]
1512 A243 Boost, transition frequency
for maximum voltage boost
(second parameter set)
rw 0 – 50 % 0.1 [%]
1513 A244 U/f characteristic (second
parameter set)
rw 00: Constant torque curve
01: Reduced torque curve
02: SLV active DV51 only
1514 A245 U/f characteristic, output
voltage (second parameter
set)
rw 0 – 255 1 [%]
1515 A246 SLV, gain factor, automatic
voltage compensation
(second parameter set)
DV51 only
rw 0 – 255
1516 A247 SLV, gain factor, automatic
slip compensation (second
parameter set)
DV51 only
rw 0 – 255
1517 A261 Maximum operating
frequency (second
parameter set)
rw 0 – 400 Hz 0.1 [Hz]
1518 A262 Minimum operating
frequency (second
parameter set)
rw 0 – 400 Hz 0.1 [Hz]
1518 A292 Acceleration time 2 (second
parameter set) (MSB)
rw 0.01 – 3000 s 0.01 [s]
1519 A292 Acceleration time 2 (second
parameter set) (LSB)
rw 0.01 – 3000 s
151A A293 Deceleration time 2 (second
parameter set) (MSB)
rw 0.01 – 3000 s 0.01 [s]
151B A293 Deceleration time 2 (second
parameter set) (LSB)
rw 0.01 – 3000 s
151C A294 Acceleration time, specify
signal for changeover from
acceleration time 1 to
acceleration time 2 (second
parameter set)
rw 00: Digital input (2CH) 0.1 [Hz]
01: Frequency (PNU A095 or A096)
151D A295 Reserved
rw
Holding
register
Function
code
Name
Access
rights
Value range Manipulated
variable
hex