Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-48
Moeller 07/01 AWB-C2700-1347GB
NOTES ON SIMATIC 7 (Continuation)
The ZB4-609-IF1 station number must be set between 1...125 (influence HSA).
Ensure, however, that each station in the MPI network is assigned a unique station number (no double
assignments).
Check with the PG under “Accessible Nodes”, which stations are already assigned.
Station number 0 is reserved for the PG.
Station number 2 is the default setting for the PLC
The HSA (Highest System Address) must be the same for all stations in the network (15, 31, 63 or 126).
If declaration is wrong or missing, the ZB4-609-IF1 will use 126.
As soon as the ZB4-609-IF1 is connected with a PLC in the MPI network, you will see this under the set
station number in the PG under “Accessible Nodes”.
The PG cannot, however, be used to establish a connection to this station. If, however, this is attempted,
the ZB4-609-IF1 will refuse this connection. The PG will then output the message “Station refuses
connection establishment”.
The ZB4-609-IF1 can establish active connection with up to 42 MPI stations (SIMATIC S7 PLC) at the
same time.
The individual data blocks can be assigned as follows :
– 1 Byte Destination station (MPI station number)
– 1 Byte Data type (Byte, Word, Dword)
– 1 char Data type (“D” = DB:DBB, “M” = MB, “E” = EB, “A” = AB)
– 1 word Module address (Only with data type D corresponds to the DB number)
– 1 word Data address
In the case of conflicting data types (byte, word, Dword), the data cannot be stored correctly in the PLC.
e. g. Word value as data type Byte ===> LO/HI byte reversed
An error message will be output if the set destination station (PLC) is not available or if the network is not
connected.
The number after ST# corresponds to the missing MPI station number in hexadecimal format.
MPI 1.52 ST#02 CONNECT?
If the module address or data address is not available, the following message is output:
MPI 1.51 ST#09 ADDRESS!
Since the ZB4-609-IF1 always transfers data blocks of at least 2 bytes, only the access to the data
address is checked and not the subsequent addresses.
Following addresses that are not present are ignored and do not initiate error messages.
If no errors occur with the data transfer, the following message will be output:
MPI 1.51 ST#06 READY!
The messages and error messages are generated by the ZB4-609-IF1 after every data transfer. These,
however, are only displayed in the MMI in the event of a change (error after Ready) or sporadically if the
error stays the same.