Communications Card Description ZB4-601-IF1, ZB4-609-IF1 4-49
Moeller 07/01 AWB-C2700-1347GB
9.2 B & R
B & R
PLC Type Protocol PLC Port Parameter
CP60
Mininet PP40 Mininet 19200 baud, 8 data bits, 1 stop bit, no parity
DRIVER DESIGNATION ALT : MININET > SPOIO Mode (MININET.BIN)
DRIVER DESIGNATION ALT : MININET > PLC Mode (MININET.BIN)
SUPPORTED DATA TYPES : R, F (only with SPOIO)
WIRING LIST
RS 232
Signal Pin Pin Signal
RxD 2 3 TxD
TxD 3 2 RxD
SG 5 7 SG
ZB4-601/609-IF1 PP40-Mininet
(9 pole male)
(25 pole male)
NOTES
The connection to the B & R CP60 is made via the additional module PP40.
The firmware of the PP40 must be created with the appropriate drivers for PLC mode or SPOIO mode
(see PP40 documentation) and must match the driver selected for the MMI.
The ZB4-601/609-IF1 card must be set to “ALT” and the current Mininet driver (MININET.BIN) must be
loaded (see section 3.1).
The PLC program does not require any other drivers or interpreters and active communication is started
immediately.
As Mininet is a Master/Slave network, ensure that the destination address of the data block is the same
as that of the PLC. The MMI has the permanently assigned address 0 and is always the master.
Only the register types “R” can be used with the driver for PLC mode. With the driver for SPOIO Mode
type “F” markers can also be addressed.
Data is exchanged bytewise with the PLC. Words and double worlds are stored directly in Motorola
format.
Examples :
Byte1 R100
Word1 R101(HB) R100 (LB)
Dword1 R103(HW/HB) R102 (HW/LB) R101 (LW/HB) R100 (LW/LB)
HB = Higher Byte, LB = Lower Byte, HW = Higher Word, LW = Lower Word