T200 User's Manual SECTION 3: WIRING AND INSTALLATION
PAGE 3-42
3.11 Paralleling T200-X10 Units through the D.C. Bus
T200-X10 units can be paralleled via the D.C. Bus, in order to share regeneration power. In Figure 3.19, below, the
T200-X10 units are shown with the a.c. mains inputs connected to all T200-X10 units. The user can also connect the
D.C. Bus outputs of the T200-X10's at TB3 in order to share regeneration power.
1 2 3 4
L1 L2 L3 PE
Connector TB2
1 2 3
DC+ DC- PE
Connector TB3
T200-X10
12AWG (4.0mm
2
) Wire
Twist DC+ and DC- Wires
1 2 3 4
L1 L2 L3 PE
Connector TB2
1 2 3
DC+ DC- PE
Connector TB3
T200-X10
a.c. Mains
L1
L2
L3
Protective
Earth
To further
paralleled
T200-
X10's
12AWG (4.0mm
2
) Wire for T200-3/4/5
8AWG (10.0mm
2
) Wire for T200-6/7
Figure 3.19: Paralleling T200-X10 Units through the D.C. Bus
CAUTION:- If a T200-X10 unit does not see a high a.c. voltage at pins 1, 2 or 3 of
terminal TB2, then the T200-X10 will continuously activate the fast bus discharge.
This will cause damage to the internal regeneration circuitry, if a high d.c voltage is
present at connector TB3. The T200 will then have to be returned to the factory for
repair.