DISPLAY AND MENU OPTIONS
Table 10. Smart DC Controller - Installer Menu Functions
Ref.
No.
User Menu
Display
Setting Options
(Bold = Factory
Settings)
Menu Tasks and Explanations
Associated
DC
Controller
Display
Connections
30
IR 1 REVERSE
INSIDE OBS LOOP
0 = Pause closing
only
1 = Enable
reversing to open
Default is for full reversal when
Inside Obstruction Loop is
triggered while closing. A setting
of 0 causes gate to only pause
when triggered. Closure begins as
soon as loop is clear again.
INSIDE OBS
LOOP COM
or Hy5B
31
DL 1 STANDARD
DETECTOR LOGIC
1 = Standard
2 = Quick closed
3 = Forced Time out
4 = Full anti-tailgate
This selection determines whether
close timer begins to count down
after vehicles have departed
detector loops or whether close
timer will count down while the
loops are occupied. Gate can only
close when all loop detectors are
clear.
Default settings causes Close
Timer to start when all loops are
clear. A setting of 2 causes Close
Timer to start when open limit
is reached. A setting of 3 forces
the Close Timer to 0 when the
OOLD and IOLD are tripped
simultaneously. A setting of 4
stops the gate when OOLD and
IOLD are tripped simultaneously
and closes from that point when
the loops clear.
Hy5B
SlideSmart HD Programming and Operations
6060
support.hysecurity.com