3-16
3.5.5 Sequence Mode Answerback Reading
This is the area where the sequence mode selected in the Sequence Mode Selection Area is stored.
“1” is stored in the bit corresponding to the selected sequence mode. “0” is stored in other bits.
“0” is stored when the manual mode is changed to anything other than RUN or TEST.
3.5.6 Sensor Binary Current Position Value Reading
The machines current position within the scale length is detected by the ABSOCODETR sensor, and
that position value is stored in this area as a sensor binary values
The ranges for sensor binary current position values are as follows:
0 131071 (0 1FFFF#)
3.5.7 Scaling Binary Current Position Value Reading
The sensor binary current position value is converted to mm or ‘inch’ units, and the current position
minimum valueis then added to produce the scaling binary current positionvalue which is stored in
this area.
The scaling binary current position value =
Scaling length value / 131072×Sensor binary valueCurrent position minimum value