EasyManuals Logo
Home>NSD>Controller>Varlimit VS-212DN

NSD Varlimit VS-212DN User Manual

Default Icon
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
6-6
6.3.4 Current position value setting (I/O address: 16396 [16460])
This section explains how to set the current position value. the current position valuesetting consist
of designating a numeric value which corresponds to a given machine position.
For exampleif the machine is moved to its 100 mm position (or any desired position), the current
positionsetting which corresponds to that position would be designated as 10000(when resolution
is 0.01). The current position setting provides a reference value on which the detection range
([minimum current position value] to [minimum current position value + scale length 1]) is based.
Setting sequence:
(a) Move the machine to the desired setting position.
(b) Turn the PLC Ready signal (command 1: 7 bit) OFF.
(c) Set “1” to initial setting and write select bit of I/O address 4 (B1 and B4).
(d) Write the setting value to buffer memory addresses 16396 (16460).
(e) Turn the PLC Ready signal ON.
(f) Writing is completed when operation status (status 1: 7 bit) has turned ON.
Notes:
o Current position settings are executed simultaneously for 2 axes. To designate settings at each
axis individually, use the current position preset function.
o Depending on the minimum unit of current position change (resolution), there may be cases in
which the current position value will vary slightly from the current position setting value. When the
current position value is between the minimum units, the larger value will be selected.
Ex.) Current position value change: 0 7 15
Current position setting value: 10
Because the current position setting value is between 7 and 15, the larger value of 15will
be designated as the current position value.
Important:
Current position value setting shall not exceed 10000 times. If exceeding this, use current position
preset function.
CURRENT POSITION VALUE
This value indicates where the machine is currently positioned within the machine detection range.
This can be expressed in two ways: By a sensor binary current position value, or by a scaling binary
current position value.
(a) Sensor binary current position value:
With this format, the machines current position within the scale length is detected by the
ABSOCODER sensor, and that position value is expressed as a sensor binary value’.
ABSOCODER sensor detection ranges: 0-131071 (1FFFFHEX)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the NSD Varlimit VS-212DN and is the answer not in the manual?

NSD Varlimit VS-212DN Specifications

General IconGeneral
BrandNSD
ModelVarlimit VS-212DN
CategoryController
LanguageEnglish