Programless Communications Section 5-1
The Request Bits are set to the following values.
Note To change the Request Bits, first set the Request Bits to 0000 then change
the setting. The same applies when periodically executing the same operation
command.
Example: Changing a Single Action to a Multi Action
1,2,3... 1. For a single action, the Response Bits are set to the single action value,
0001.
Note The Request Bits cannot be changed directly to 0002 because the
setting will not be accepted.
2. Change the Request Bits to 0000, then confirm that the Response Bits
have been set to 0000.
3. Then change the Request Bits to the multi action setting of 0002.
Each set of Request Bits has a corresponding set of Response Bits. Once
the Request Bits have been set, the Response Bits operate in the order
shown in the following table.
Bits Value Action
Read Request
Bits
0000: Stop operation Stops operation after a series of operations has been completed.
0001: Single Reads the parameters set in the Programless Upload Setting Area once.
0002: Multi Continuously reads the parameters set in the Programless Upload Setting Area.
0003: Read setting Reads the parameters set in the Programless Download Setting Area and writes
them to the read area.
Setting Change
Request Bits
0000: Stop operation Stops operation after a series of operations has been completed.
0001: Single Changes only the parameters set in the Programless Download Setting for which
values have been changed.
0002: Multi Continuously repeats the operation of changing only the parameters set in the
Programless Download Setting for which values have been changed.
Operation
Command
Request Bits
0000: Stop operation Stops operation after a series of operations has been completed.
0001: Single Executes the operation command set in the Operation Command Code.
0002: Multi Executes the operation command each time the value in the Operation Command
Code changes.