Programless Communications Section 5-1
■ If Not Operating Correctly
Check the following items if the operation is incorrect.
• Are the wiring and settings correct?
• Was the power turned OFF once the EJ1 and PLC settings had been
completed? (The EJ1 settings are enabled only after the EJ1 is reset.)
• The Programless Communications Receive Wait Time may be too short.
Refer to Adjusting Communications Time with PLC on page 121 and
change to a longer wait time.
5-1-3 Detailed Settings
Link Data Settings Link data settings are made to set which EJ1 values to monitor or change.
• Monitor
The parameters to be monitored are set under Programless Upload Set-
tings.
The HFU collects monitor values based on these settings for the Units con-
nected to the HFU and transfers the values to PLC memory.
• Changing Settings
The parameters to be changed are set under the Programless Download
Settings.
The HFU reads the values in a PLC memory area according to these set-
tings and then refreshes the settings for Units connected to the HFU.
Variable type
D7/97
Address Programless Upload Setting
304
0000 Reserved (Read Response Bits)
0001 Reserved (Setting Change Response Bits)
0002 Reserved (Operation Command Response Bits)
0003 Reserved (Communications Status)
300
0004 Parameter A to be monitored
0005 Parameter B to be monitored
•
•
•
012F
Variable type
D8/98
Address Programless Download Setting
304
0000 Reserved (Read Request Bits)
0001 Reserved (Setting Change Request Bits)
0002 Reserved (Operation Command Request
Bits)
0003 Reserved (Operation Command Code)
300
0004 Parameter A to be changed
0005 Parameter B to be changed
•
•
•
012F