EasyManua.ls Logo

Omron EJ1

Omron EJ1
253 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
135
Programless Communications Section 5-1
Details of Operation
Command Codes for
Programless
Communications
(1) 0: Specified Unit; 1: All Units
(2) 0: According to related information; 1: All channels
(3) 00: Backup; 01: RAM
(4) 00: Channel 1, 01: Channel 2, 10: Channel 3, 11: Channel 4
(5) 00: Clear, 01: Register
Example: Operation Command Code to execute Run for channel 1 of
Unit No. 1
All channels specified
Related Information
All Units specified
Command code Unit specification
bit
15 14 13 12 11 10 9 8 7 6 5 43210
Write Mode
0 0 0 100
No. 0
(See
note
1.)
(See note 3.)
0
Software Reset
0 0 0 110 00 0
Run
0 0 1 010 (See note
4.)
(See
note
2.)
Stop 0 0 1 011
Manual 0 0 1 100
Auto 0 0 1 101
000 0 0 0
40% AT Execute
0 0 1 110
No. 1
100% AT Execute 0 0 1 111
000 0 0 1
AT Cancel
0 1 0 000
No. 2
Bank 0 Change 0 1 1 110
000 0 1 0
Bank 1 Change
0 1 1 111
No. 3
Bank 2 Change 1 0 0 000
000 0 1 1
Bank 3 Change
1 0 0 001
···
Local SP Change 1 0 0 010
Remote SP Change 1 0 0 011
Reset Error 1 0 1 101
No. 31
000
Alarm 1 Latch Cancel
1 1 0 010 (See note
4.)
(See
note
2.)
011 1 1 1
Alarm 2 Latch Cancel
1 1 0 011
Alarm 3 Latch Cancel 1 1 0 100
All Alarm Latch Cancel 1 1 0 101
Save RAM Data 1 1 0 111 001
Register Unit Configuration
1 1 1 011
(See note 5.)
0
Command code for Run Unit specification: 01 Channel 1
0 0 1 010000 0 0 10000
H’ 2 H’8 H’ 1 H’ 0
H’ 2810

Table of Contents