*1. For a broadcast, no response will be sent back.
*2. Note that the holding register start address for F001(LOW) is 0001 hex, which is 1 less than the register num-
ber 0002 hex: Register address = Register number - 1.
Note that, except for F001, changing the parameter value on the data display does not update the dis-
played data realtime. To view the updated value, once return to the parameter display and then display
the data again.
If the Write to Holding Register function is not executed normally, refer to 8-5-9 Exception Response on
page 8-20.
8-5-5 Loop-back Test [08 hex]
Checks the communications between the master and the slave. Any value can be used for test data.
⚫
Query