5 Basic Settings
5 - 11
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter No.
Function name
Data
Default data
Unit
b049
Heavy load/Light Load
Selection
00: Heavy load mode (CT)
01: Light load mode (VT)
00
Item
Heavy load (CT)
Light load (VT)
Feature
Loads that require a high torque during
acceleration/deceleration etc.
Loads that do not require frequent use of
the inverter above rated torque
Application example
Elevator, crane, conveyor, etc.
Fan pump, air conditioner, etc.
Rated output current
(Example)
3.0 A (3-phase 200-V, 0.4-kW inverter)
3.5 A (3-phase 200-V, 0.4-kW inverter)
Overload current rating
150%, 60 s
120%, 60 s
5
5-2 V/f Control Settings
5-2-2 Heavy load/Light Load Selection