5 Basic Settings
5 - 11
Multi-function Compact Inverter 3G3MX2-EV2 User’s Manual (I666-E1)
Parameter No.
Function name
Data
Default data
Unit
b049
Heavy load/Light Load
Selection
00: Heavy load mode (CT)
01: Light load mode (VT)
00
Item
Heavy load (CT)
Light load (VT)
Feature
Loads that require a high torque during
acceleration/deceleration etc.
Loads that do not require frequent use of
the inverter above rated torque
Application example
Elevator, crane, conveyor, etc.
Fan pump, air conditioner, etc.
Rated output current
(Example)
3.0 A (3-phase 200-V, 0.4-kW inverter)
3.5 A (3-phase 200-V, 0.4-kW inverter)
Overload current rating
150%, 60 s
120%, 60 s
5
5-2 V/f Control Settings
5-2-2 Heavy load/Light Load Selection

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron MX2 Series and is the answer not in the manual?

Omron MX2 Series Specifications

General IconGeneral
Cooling MethodFan cooling
Output Frequency Range0.1 to 400 Hz
Control MethodV/f control, Sensorless vector control
Protection FunctionsOvercurrent, overvoltage, undervoltage, overload, overheating, short circuit
Communication OptionsModbus RTU
Overload Capacity150% for 60 seconds
Braking UnitBuilt-in
Ambient Operating Temperature-10°C to +50°C
EnclosureIP20
Storage Temperature-20°C to +65°C
Humidity5 to 95% RH (non-condensing)
AltitudeUp to 1000m
Power Supply Voltage200-240V AC
Input Voltage3-phase 200-240V AC