Verify a Fan Module
5.
Close the fan door.
6.
Verify that the Top Fan Fault LED on the front of the server and the Service
Required LEDs on the front and rear of the server are extinguished.
7.
Consider your next step:
■ If you installed the fan module as part of another procedure, return to that
procedure.
■ Otherwise, return the server to operation. See “Returning the Server to
Operation” on page 145.
Related Information
■
“Returning the Server to Operation” on page 145.
■
“Remove a Fan Module” on page 63
■
“Verify a Fan Module” on page 66
Verify a Fan Module
1.
Verify that the Service Required LED on the replaced fan module is not lit.
See “Fan Module LEDs” on page 62.
2.
At the Oracle ILOM prompt, start the fault management shell.
-> start /SP/faultmgmt/shell
Are you sure you want to start /SP/faultmgmt/shell (y/n)? y
faultmgmtsp>
3.
Type fmadm faulty to check for faults.
■
If faults are reported, see “Detecting and Managing Faults” on page 21.
■
If no faults are reported, then the component has been replaced successfully.
4.
Consider these possibilities:
■
If any of the LEDs are illuminated, see “Fan Module LEDs” on page 62.
■
If none of the LEDs are illuminated, the fan module has been replaced successfully.
66 SPARC S7-2 Server Service Manual • March 2017