Remove a Fan Module
Remove a Fan Module
This is a hot-service procedure that can be performed by a customer while the server is running.
Caution - Do not remove a fan without installing a replacement fan to ensure adequate cooling
and maintain server availability.
1.
Prepare for servicing.
See “Preparing for Service” on page 33.
2.
Extend the server to the maintenance position.
See “Extend the Server to the Service Position” on page 41.
3.
To open the server fan door, slide the fan door latches to the front of the server
and swing the door up to the open position.
Caution - Close the server fan door within 60 seconds to maintain adequate airflow to properly
cool the server. Leaving the door open for more than 60 seconds, while the server is running,
might cause the server to overheat and shut down.
4.
Identify the faulty fan module by locating the fan with the amber fault LED lit.
See “Fan Module LEDs” on page 62.
5.
Remove the faulty fan module.
Servicing Fan Modules 63