Push buttons on the Fire Brigade Panel (FBP)
Push button
Operation/function
P1
Alarms queued (black)
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
P2
Silence buzzer
(yellow)
Used to silence the buzzer in EBL128
P3
Silence Alarm devices
(red)
5
Used to silence the sounders (i.e. to "reset" outputs for alarm
devices).
6
P4
Reset (green)
Used to reset the fire alarm(s).
7
Has to be pressed for > 0.5
sec.
P5
Evacuate (green)
8
Used to activate all the sounders (i.e. the outputs for alarm
devices).
Alert Annunciation
Acknowledge (green)
9
Used to acknowledge an Alert Annunciation alarm.
Disable (yellow)
10
Used to disables all zones in alarm state.
5
In the New Zealand convention = The "inside switch".
6
Via EBLWin can be set if the alarm devices shall be continuous off /
disabled or re-sound for a new alarm.
7
Single reset: The fire alarm displayed in the LCD (first row to the left)
will be reset. When more than one fire alarm is activated (LEDs "Alarms
queued" are lit) each fire alarm has to be individually reset.
Multiple reset (Default): All fire alarms will be reset simultaneously.
Single encapsulated reset: Like Single reset but with the Encapsulation
function, which is described in chapter "Single with automatic disablement",
page 55.
NOTE (1)! When "Multiple reset" is used, encapsulated reset can be done
by pressing "Reset" (P4) and 0.1 sec. later also press "Alarms queued" (P1)
and hold them pressed for > 0.5 sec. The fire alarm displayed in the LCD
(first row to the left) will be encapsulated or the points in alarm status within
one zone will be encapsulated or the whole zone (conventional) will be
encapsulated.
NOTE (2)! When "Single encapsulated reset" is used, you can make a
"Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also press "A" (in
the keypad) and hold them pressed for > 0.5 sec.
8
"Evacuate" is only valid in the "Belgian", Brittish Standard, Hungarian,
Spanish and "Ukrainian" conventions.
9
"Alert Annunciation Acknowledge" is only valid in the "Czech", Bulgarian
and "Polish" conventions.
10
"Disable" is only valid in the "Australian" and New Zealand conventions.