MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
64
FAULT: Mains
* Loss of mains, i.e. no 230 V AC (the fault is activated
after 1-300 minutes).
54
* Fuse for 230 V AC blown.
* Fuse "F1" on the main board 4556 blown.
FAULT: Mains, external power supply
Loss of mains, i.e. no 230 V AC to the ext. power supply equipment
(the fault is activated after 1-300 minutes).
54
Check 230 V AC fuses.
A fault output is connected to a programmable input in the EBL128
system. Check the input as well.
FAULT: Mains, techn address xxx
This is valid for an external power supply (e.g. 3366) connected on the
COM loop.
* Loss of mains, i.e. no 230 V AC in the loop unit (the fault
is activated after 1-300 minutes).
55
* Fuse for 230 V AC blown.
* Fuse "F1" blown on the charger board 3367.
FAULT: No reply zz-aa
Press "" to see the technical address.
FAULT: No reply techn address xxx
zz-aa = Zone-Address. xxx = COM loop address.
In spite of communication in both directions (COM loop A-direction
and B-direction), the unit cannot be found.
* Check the unit's address (with the address setting tool
3314/4414).
* Faulty unit.
* Detector might be removed (un-plugged) from its base.
* Double break or short-circuit on the COM loop.
(Note! There will also be a fault message "FAULT: Cut-off
loop…." or "FAULT: Short-circuit loop….".).
*
FAULT: No reply AAU x
54
The time is programmable in EBLWin. Max. 30 min. according to the
EN54-2 standard. Default value depending convention.
55
The time is programmable in EBLWin. Max. 30 min. according to the
EN54-2 standard. Default value depending convention.