AAU=1735 / 1736. (Alert Annunciation Unit)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
EPU=1728. (Ext. Presentation Unit)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
FAULT: No reply, expansion board x
Valid for the 8 zones exp. board 4580, the 8 relays exp. board 4581
and the Inputs and outputs exp. board 4583 mounted in the c.i.e.
(EBL128). Also valid for the I/O Matrix board 4582 connected on the
COM loop, i.e. mounted outside the c.i.e.
EBL128 cannot communicate with the board. Check / edit the
address. Check the cables / connections.
FBP=1826 / 1828. (Ext. Fire Brigade Panel)
EBL128 cannot communicate with the unit. Check / edit the address
and the S/W mode in the unit (or edit the SSD).
This is valid for the EBL128 supervised voltage outputs S0 and S1.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for a fire brigade tx (type Routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
* Calibration not performed via menu H5/A1.
* Short-circuit / break on the connected cable / equipment.
* Blown fuse "F8" (S0) or "F6" (S1) on the main board
4556.
* Connected equipment might be "missing".
* End-of-line resistor(s) missing or not correct value (see
drawing 128-22). 1- 5 resistors 33K.
NOTE! The calibrated value has to be in the range 4K7-50K.