MEW01623 Rev: - EBL128 Operating Instructions V2.0.x
66
FAULT: Output x expansion board x
A fault on the supervised output x on the expansion board (4583) with
address x.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
* Calibration not performed via menu H5/A1.
* Short-circuit / break on the connected cable / equipment.
* Blown fuse "F1" (Output 0) or "F2" (Output 1) on the
4583 board.
* Connected equipment might be missing.
* End-of-line resistor(s) missing or not correct value (1-5 x
33K).
NOTE! The calibrated value has to be in the range 4K7-50K.
FAULT: Output x, techn addr xxx
This is valid for COM loop output unit 3364 outputs.
If the output is programmed for sounders (type Alarm devices), it is
also indicated by LED "Fault / Disablements Alarm devices" (L13)
blinking.
If the output is programmed for fire brigade tx (type Routing
equipment), it is also indicated by LED "Fault / Disablements Fire
brigade tx" (L15) blinking.
* Calibration not performed via menu H5/A1.
* Short-circuit / break on the connected cable / equipment.
* Connected equipment might be "stolen".
* End-of-line capacitor(s) missing or not correct value (see
drawing 128-28).
NOTE! The calibrated value has to be in the range 470 nF 5 x
470 nF (2350 nF).
FAULT: Read/write site data (SSW)
SSW = the data that is changed during operation, i.e. week average
sensor values, passwords, calibration values and event logs.
If the C.U. was made powerless (i.e. mains and battery
disconnected) without first doing a Safe shut down of control
unit via menu H8/S7 (see page 132), this fault might be
generated when the C.U. is powered again. After fault
acknowledge the SSW will get default values and the fault
will be corrected (serviced). Supervised outputs have to be