4-24
Note
Related page
•Aparameterisdesignatedasfollows:
Pr0.00
Parameter No.Class
•ForparameterswhichNo.haveasuffixof“
*
,changedcontentswillbevalidatedwhen
youturnonthecontrolpower.
•P.3-32...“InputsandoutputsonconnectorX4”
Pr2.05
2ndnotchwidthselection
Range Unit Default
Related
control mode
0 to 20 2 P S T F
Caution
Setthewidthofnotchatthecenterfrequencyofthe2ndnotchlter.
Higherthesetup,largerthenotchwidthyoucanobtain.Usewithdefaultsetupinnormaloperation.
Pr2.06
2nd notch depth selection
Range Unit Default
Related
control mode
0 to 99 0 P S T F
Caution
Setthedepthofnotchatthecenterfrequencyofthe2ndnotchlter.
Higherthesetup,shallowerthenotchdepthandsmallerthephasedelayyoucanobtain.
Pr2.07
3rd notch frequency
Range Unit Default
Related
control mode
50 to 5000 Hz 5000 P S T F
Caution
Notchfrequencyisautomaticallysettothe1stresonancefrequencyestimatedbytheadaptivelter.
Innoresonancepointisfound,thefrequencyissetto5000.
Pr2.08
3rdnotchwidthselection
Range Unit Default
Related
control mode
0 to 20 2 P S T F
Caution
Setthewidthofnotchatthecenterfrequencyofthe3rdnotchlter.
Higherthesetup,largerthenotchwidthyoucanobtain.Usewithdefaultsetupinnormaloperation.
Whentheapplicablelterfunctionisused,parametervalueisautomaticallyset.
Pr2.09
3rd notch depth selection
Range Unit Default
Related
control mode
0 to 99 0 P S T F
Caution
Setthedepthofnotchatthecenterfrequencyofthe3rdnotchlter.
Higherthesetup,shallowerthenotchdepthandsmallerthephasedelayyoucanobtain.
Whentheapplicablelterfunctionisused,parametervalueisautomaticallyset.
Pr2.10
4th notch frequency
Range Unit Default
Related
control mode
50 to 5000 Hz 5000 P S T F
Caution
Notchfrequencyisautomaticallysettothe2ndresonancefrequencyestimatedbytheadaptivelter.
Thenotchlterfunctionwillbeinvalidatedbysettingupthisparameterto"5000".
Pr2.11
4thnotchwidthselection
Range Unit Default
Related
control mode
0 to 20 2 P S T F
Caution
Setthewidthofnotchatthecenterfrequencyofthe4thnotchlter.
Higherthesetup,largerthenotchwidthyoucanobtain.Usewithdefaultsetupinnormaloperation.
Whentheapplicablelterfunctionisused,parametervalueisautomaticallyset.
1. Details of parameter
[Class 2] Damping control
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: CustomerService@valin.com