3. Troubleshooting
When in Trouble
Motor Does Not Run
When the motor does not run, refer to P.2-102, "Display of Factor of No-Motor Running" of Preparation
as well.
Classication
Causes Measures
Parameter Setup of the
control mode is
not correct
Check that the present
control mode is correct
with monitor mode of the
front panel.
1) Set up Pr0.01 again.
2) Check that the input to control mode switching
(C-MODE) of the Cnnector X4 is correct, when
Pr0.01 is set to 3 to 5.
Selection of
torque limit is not
correct
Check that the external
analog input (N-ATL/
P-ATL) is not used for the
torque limit.
1) Set up Pr05.21 to 0 and apply -9 [V] to N-ATL and
+9 [V ] to P-ATL when you use the external input.
2) Set up Pr05.21 to 1 and set up the max. value to
Pr0.13 when you use the parameter value.
Setup of
electronic gear
is not correct.
(Position/Full-
closed)
Check that the motor
moves by expected
revolution against the
command pulses.
1) Check the setups of Pr0.09, Pr0.10 and Pr5.00 to
Pr5.02 again.
2) Connect the electronic gear switching input (DIV) of
Connector X4 to COM–, or invalidate the division/
multiplication switching by setting up the same
value to Pr0.09 and Pr5.00.
Wiring Servo-ON input
of Connector
X4 (SRV-ON) is
open.
In the front panel monitor
mode, is the Pin No.
corresponding to SRV-
ON in “ - ” state?
Check and make a wiring so as to connect the SRV-
ON input to COM–.
Positive/negative
direction over-
travel inhibit input
of Connector X4
(NOT/POT) is
open.
In the front panel monitor
mode, is the Pin No.
corresponding to NOT/
POT in “ A ” state?
1) Check and make a wiring so as to connect both
NOT/POT inputs to COM–.
2) Set up Pr5.04 to 1 (invalid) and reset the power.
Command pulse
input setup
is incorrect.
(Position/Full-
closed)
Check that the input
pulse counts and
variation of command
pulse sum does not slips,
with monitor mode of the
front panel.
1) Check that the command pulses are entered
correctly to the direction selected with Pr0.05.
2) Check that the command pulses are entered
correctly in the format selected with Pr0.07.
Command
pulse input
inhibition (INH) of
Connector X4 is
open. (Position/
Full-closed)
In the front panel monitor
mode, is the Pin No.
corresponding to INH in
“ A ” state?
1) Check and make a wiring so as to connect the INH
input to COM–.
2) Set up Pr5.18 to 1 (invalid).
Counter clear
input (CL) of
Connector X4
is connected to
COM–. (Position/
Full-closed)
In the front panel monitor
mode, is the Pin No.
corresponding to CL in
“ A ” state?
1) Check and make wiring so as to open the CL input
2) Set up Pr5.17 to 0 (invalid).
Related page
• P.2-88... “How to Use the Front Panel” • P.3-32 “Inputs and outputs on connector X4”
• P.4-6 to P.4-85... “Details of parameter”