4-84
Note
Related page
•Aparameterisdesignatedasfollows:
•ForparameterswhichNo.haveasuffixof“
*
”,changedcontentswillbevalidatedwhen
youturnonthecontrolpower.
•P.3-32...“InputsandoutputsonconnectorX4”
Default: [ ]
4
1. Details of parameter
Setup
[Class 7] Special setting
Pr7.14
Mainpowerturn-offwarningdetectiontime
Range Unit Default
Related
control mode
0 to 2000 ms 0 P S T F
Setsthetimeelapsedbeforethemainpowerturn-offwarningisdetectedwhenamain
powerturn-offstatecontinues.
0to9,2000:Warningdetectiondisabled
10to1999:Warningdetectionenabled(unitshowninms).
Note)Tocausethewarningdetectiontooccurearlierthanturn-offdetection,maintainthe
relationship"Pr7.14<Pr5.09"whenthisparameterisset.
Inaddition,whenthetimesetforPr7.14islongandtheP-Nvoltageatthemainpower
converterareaisreducedtothespeciedvalueorbelowbeforethewarningisdetected,
Err13.0"Mainpowerinsufcientvoltageprotection"isinvokedearlierthanthewarning.
Pr7.22
Special function enhancement setting 1
Range Unit Default
Related
control mode
−32768to32767 — 0 P S T F
Setsvariousfunctioninbitunits:
bit
Function Setup value
bit0-3 Notused Fixedto0.
bit4
externalscalepositioninformationmonitorfunction
setting under semi-closed control
0:Invalid 1:Valid
bit5-15 Notused Fixedto0.
*bit 0 is the least signicant bit.
*For bit 4 (external scale position information monitor function setting under semi-closed
control”), external scale position information can be monitored regardless of the setting
of this bit, in case of full closed control.
All other parameters will be manufacturers use.Please do not change the default
parameters.