Following alarm will be displayed when making the front panel to alarm execution mode
of monitor mode.
7
2. Absolute system
Supplement
Display of Battery Alarm
How to Clear the Battery Alarm
Replace the battery for absolute encoder when battery alarm occurs according to P.7-12,
"How to Replace the Battery". After replacement, clear the battery alarm in the following
3 methods.
(a)
"Connector X4" Connecting Alarm clear input (A-CLR) to COM– for more than 120 ms.
(b) Executing the alarm clear function in auxiliary function mode by using the front panel.
(c) Click the "Battery warning" Clear button, after select the "Absolute encoder" tab in the
monitor display window by using the PANATERM (option).
....... No alarm condition
...... Highest priority alarm
Alarm number
• Press to scroll alarm conditions.
• Kinds of alarm
alarm
No.
Alarm Content
Latched
time
*
1
A0 Overload protection Load factor is 85 % or more the protection level. 1 s to 10 s or ∞
A1 Over-regeneration alarm Regenerative load factor is 85% or more the protection level. 10 s or ∞
A2 Battery alarm Battery voltage is 3.2 V or lower. Fixed at ∞
A3 Fan alarm Fan has stopped for 1 sec. 1 s to 10 s or ∞
A4 Encoder communication alarm
The number of successive encoder communication errors
exceeds the specied value.
1 s to 10 s or ∞
A5 Encoder overheat alarm The encoder detects overheat alarm. 1 s to 10 s or ∞
A6 Oscillation detection alarm Oscillation or vibration is detected. 1 s to 10 s or ∞
A7 Lifetime detection alarm
The life expectancy of capacity or fan becomes shorter than the
specied time.
Fixed at ∞
A8 External scale error alarm The external scale detects the alarm. 1 s to 10 s or ∞
A9
External scale communication
alarm
The number of successive external scale communication errors
exceeds the specied value.
1 s to 10 s or ∞
AC Deterioration diagnosis warning
Load characteristic estimates and torque command under
constant speed has exceeded the set range.
1 s to 10 s or ∞
C3 Main power off warning
In case that Pr7.14 (Detection time of main power off warning)
is 10 to 1999, the mains power between L1 and L3 has stopped
instantaneously for more than the time prescribed in Pr7.14.
1 s to 10 s or ∞
*1 Alarms can be cleared by using the alarm clear. Because the all existing alarms are kept cleared while the
alarm clear input (A-CLR) is kept ON, be sure to turn it OFF during normal operation. Either 1 s-10 s or
can be
selected by using user parameter.
Exception: Battery alarm is xed at ∞ because it is latched by the encoder.
Because the end of life alarm means that the life expectancy cannot be extended, the alarm is set at ∞.
P.2-98“Alarm Clear Screen” • P.3-33 “Inputs and outputs on connector X4”
P.7-26 “Outline of Setup Support Software, “PANATERM””