Relationship between Wire Diameter and Permissible Current
Caution
Caution
When selecting a cable, refer to the following selection guide showing relationship be-
tween cable specication and current carrying capacity.
Example: Power supply 3-phase, 200 V, 35 A, ambient temperature 30 °C
Determine the fundamental permissible current according to the
cable conductor material (example: stranded copper wire). (For the
purpose of this example, the ampere indicated by
is selected from
the table right.)
Next, determine the number of conductors. (In this example, the
cable contains 4 conductors (3 + ground).) Determine the applicable
permissible current using the following formula.
Applicable permissible current
=
fundamental permissible current x current reduction coefcient x current
correction coefcient
= 37 x 0.7 x 1.414
.
=. 36.6 (A)
This permissible value is larger than 35 A to be carried though the
cable. Therefore, according to the list of recommended eco-cables,
the cable to be selected for the cable with nominal cross section 3.5
mm
2
is a polyethylene-insulated heat-resistant 4-conductor power
cable having 13.5 mm nish O.D. (approx. 14.5 mm with shield).
<Supplement>
The current correction coefcient is determined using the following formula:
(Max. permissible temp. – ambient temp.) ÷ 30
The current correction coefcient is determined according to the cable. Check the specication of the cable
used.
The current reduction coefficient is provided for the case
where the cable (4-conductor cable in the case of example),
is housed in plastic race/sheath, plastic tube, metal race/
sheath, metal tube or exible conduit.
Because the neutral conductor is not counted as a wire, the cur-
rent reduction coefcient for “3 or less” is applied as indicated by
(
) in the table right.
Conductor
Insulation
thickness
(mm)
Sheath
thickness
(mm)
(Reference)
Finish O.D.
(mm)
Max.
conductor
resistance
(20 °C)
(W/km)
Test
voltage
(V/1 min.)
Minimum
insulation
resistance
(MW•km)
(Reference)
Approx.
mass
(kg/km)
Nominal
cross
section
(mm
2
)
Structure
or shape
(wires/mm
2
)
Outside
diameter
(mm)
2 7/0.6 1.8 0.8 1.5 12.0 9.42 1500 2500 170
3.5 7/0.8 2.4 0.8 1.5 13.5 5.30 1500 2500 250
5.5 7/1.0 3.0 1.0 1.5 16.0 3.40 1500 2500 360
8 7/1.2 3.6 1.0 1.5 17.0 2.36 1500 2000 475
14
Circular
compression
4.4 1.0 1.5 19.0 1.34 2000 1500 730
22
Circular
compression
5.5 1.2 1.6 23 0.849 2000 1500 1100
38
Circular
compression
7.3 1.2 1.8 28 0.491 2500 1500 1800
60
Circular
compression
9.3 1.5 2.0 35 0.311 2500 1500 2790
100
Circular
compression
12.0 2.0 2.4 44 0.187 2500 1500 4630
150
Circular
compression
14.7 2.0 2.6 51 0.124 3000 1000 6710
200
Circular
compression
17.0 2.5 2.9 60 0.0933 3000 1500 8990
Caution
Note
Recommended eco-cable
Wire category: 4-conductor polyethylene-insulated power cable with heat-resistant polyethylene sheath
(Standard: EM JIS C 3605) Maximum permissible temperature: 90 °C
Shield will increase nish outside diameter by approx. 1 mm.
Appropriate cable should be selected to have sufcient allowance for parameters such as operating ambi-
ent temperature and current.
Current reduction coefficient, fundamental permissible current, etc., stated on this page are subject to
change due to e.g. standard revision. Consult cable manufacturers for the latest information.
5. Installation
Driver
• Current reduction coefficient
No. of wires in a tube Coefficient
Up to 3 0.70
4 0.63
5 or 6 0.56
7 to 15 0.49
16 to 40 0.43
41 to 60 0.39
61 or more 0.34
• Fundamental permissible
current
Stranded conductor
(nominal cross section: mm
2
)
Copper
wire
(unit: A)
2 to 3.5 (excl.) 27
3.5 to 5.5 (excl.) 37
5.5 to 8 (excl.) 49
8 to 14 (excl.) 61
14 to 22 (excl.) 88