EasyManua.ls Logo

Parker 890SD - Page 48

Parker 890SD
586 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
890CS & 890CD Common Bus Units
Page 4-28 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
A
B
C
D
1
2
3
4
5
6
7
E
FUTURE USE
Name Range Description
01
PUMR A+ 0-24V 24V DC enables drive operation
02
PUMR A- 0V
03
PUMR B+ 0-24V 24V DC enables drive operation
X11
04
PUMR B- 0V
Note Both inputs (PUMR A: terminals 01 & 02 and PUMR B: 03 & 04) must be at 24V to enable the drive.
PUMR is designed to prevent a motor from starting, for example: during machine maintenance.
(You could connect the operation of the inputs PUMR A and PUMR B to the placement of motor
guards/covers).
If the voltage on either pair is removed while a drive is running, the motor will coast to stop,
however, safety comes from redundancy (both pairs).
WARNING
Individually, PUMR A or PUMR B is not guaranteed to prevent a motor from starting.
PUMR is not designed as a safe means of stopping a spinning motor.
PUMR ensures mechanical safety; but not electrical safety: hazardous voltages remain in the
drive and can appear at the motor, but the voltage patterns needed to turn a motor will not be
present.
Reporting is via the Health relay (X14). Healthy = both PUMR inputs energised, the drive can
start, possibly without warning or user command. This reporting mechanism must not be used
as part of a safety system. It is intended as an indication only; its function is not guaranteed in
any way.
Refer to ? for a drawing of the PUMR internal workings.
totally
isolated
totally
isolated
Terminal X11 is for future use.