Programming
Page D-160 890CS Common Bus Supply - Frames B & D; 890CD Common Bus Drive and 890SD Standalone Drive - Frames B, C & D
8
9
10
11
B
C
D
1
2
3
4
5
6
7
E
PREF Name Block Type Range Default ro\rw Notes
27.15 LEAKAGE INDUC MOTOR DATA REAL 0.00 to 300.00 mH 75.01 mH rw 3,5
27.16 MUTUAL INDUC MOTOR DATA REAL 0.00 to 3000.00 mH 300.04 mH rw 3,5
27.17 ROTOR TIME CONST MOTOR DATA REAL 10.00 to 30000.00 ms 136.75 ms rw 3,5
27.23 TOTAL INERTIA MOTOR DATA REAL 0.0000 to 300.0000 kgm2 0.0000 kgm2 rw 5
27.24 SUPPLY VOLTAGE MOTOR DATA ENUM 0 : 230V
1 : 380V TO 460V
2 : 500V
380V TO 460V rw 3
29.01 DEFLUX TIME INJ BRAKING REAL 0.1 to 20.0 s 0.5 s rw 3,5
29.02 FREQUENCY INJ BRAKING REAL 1.0 to 500.0 Hz 9.0 Hz rw 3,5
29.03 I-LIM LEVEL INJ BRAKING REAL 50.00 to 150.00 % 100.00 % rw
29.04 DC PULSE INJ BRAKING REAL 0.0 to 100.0 s 2.0 s rw 3,5
29.05 FINAL DC PULSE INJ BRAKING REAL 0.0 to 10.0 s 1.0 s rw 3,5
29.06 DC LEVEL INJ BRAKING REAL 0.00 to 25.00 % 2.50 % rw 3,5
29.07 TIMEOUT INJ BRAKING REAL 0.0 to 600.0 s 90.0 s rw
29.08 BASE VOLTS INJ BRAKING REAL 0.00 to 115.47 % 100.00 % rw 3,5
29.09 ACTIVE INJ BRAKING BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
30.01 ENABLED KEYS OP STATION WORD 0000 to FFFF 00F0 rw
30.02 OP VERSION OP STATION WORD 0000 to FFFF 0000 ro Output
30.03 OP DATABASE OP STATION BOOL 0 : FALSE
1 : TRUE
FALSE ro Output
31.01 VIEW LEVEL ACCESS CONTROL ENUM 0 : OPERATOR
1 : BASIC
2 : ADVANCED
BASIC rw
31.02 PASSWORD ACCESS CONTROL WORD 0000 to FFFF 0000 rw
31.05 CONFIG NAME ACCESS CONTROL STRING max length is 16 chars rw
31.06 STARTUP SCREEN ACCESS CONTROL INT 0 to 32 0 rw
33.01 PARAMETER OPERATOR MENU 1 PREF 00.00 to A3.05 0 rw
33.02 NAME OPERATOR MENU 1 STRING max length is 16 chars rw