AS-i EtherNet/IP Gateway
Appendix: Codes indicated by the Display
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91 · Internet http://www.pepperl-fuchs.com
Issue date - 24.4.2007
147
82
The front panel operation is blocked. Until repowering-up the device can 
only be accessed from the host via the interface.
83
Program reset of the AS-i Control programm: The AS-i Control programm 
is being read out of EEPROM and copied into the RAM.
88 Display test while starting up the AS-i master
90
Error while changing a slave address in protected operating mode: No 
slave with address 0 existing.
91 Error while changing slave address: Target address is already used.
92 Error while changing slave address: New address could not be set.
93
Error while changing slave address: New address could only be stored 
volatilely in the slave.
94
Error while changing the slave address in protected operating mode: 
Slave has wrong configuration data.
95
The error 95 is caused by a superfluous slave and not by a missing slave. 
That is why the slave address is ocupated by this superfluous slave.
(In the protected mode the slave addresses which caused any configura-
tion error can be displayed by pressing the SET button. AS-i master without 
graphical display are not able to differentiate between a missing slave, an 
incorrect slave or a redundant slave. All incorrect addresses are displayed.
By pressing the SET button 5 sec. the displayed address starts to flash. 
Pressing the SET button again the master attempts to program the slave at 
the address 0 to the incorrect address.)