EasyManua.ls Logo

Phoenix Contact RAD-900-DAIO6

Phoenix Contact RAD-900-DAIO6
140 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
RAD-900-...
82/138
PHOENIX CONTACT 3827_en_B
The input and output data is saved in a Modbus memory map in the wireless module.
You can read or write the process data via the serial interface of the master wireless
module (RAD ID = 01) using the Modbus RTU command. The process data tables can
be found starting at “Modbus memory map” on page 100.
5.8 Starting up the RAD-900-DAIO6
5.8.1 Setting the address of the RAD-900-DAIO6 via the thumb-
wheel
For an I/O-to-I/O transmission of signals, both the RAD ID and I/O-MAP address are set
using the yellow thumbwheel on the RAD-900-DAIO6.
Addressing extension modules
Use the thumbwheel to set the address.
Press the SET button on the front of the wireless module to read the current
configuration.
The following settings can be made using the yellow thumbwheel:
The following conditions must be met:
Assign a maximum of 1 ... 99 addresses to the RAD-900-DAIO6 in the entire wireless
network. If the address is set to 01, the RAD-900-DAIO6 may only be used in point-to-
point mode with another RAD-900-DAIO6.
Wireless module in I/O data mode
The RAD-900-DAIO6 may be used to create a point-to-point or point-to-multipoint
connection with RAD-900-IFS devices. In this case, set the I/O-MAP address to between 02
and 99 using the white thumbwheel on the corresponding RAD-DAIO6-IFS extension
module(s) to match the yellow thumbwheel setting on the RAD-900-DAIO6.
The I/O-MAP address of an input module may only appear once in the network.
The input channels are directly assigned to the corresponding output channels at the
other wireless station.
Thumbwheel
setting
Description
01 ... 99 RAD ID and I/O-MAP address
01 Delivery state
**,
1* ... 9*,
*1 … *9
Settings not permitted

Table of Contents

Related product manuals