1.7 CONFIGURATION OF THE DHW PRIORITY SCHEDULE
7RDFFHVVWKHFRQ¿JXUDWLRQSDUDPHWHUVLQVHUWSDVVZRUG
1.8 CONFIGURATION OF THE ANTI-LEGIONELLA FUNCTION
7RDFFHVVWKHFRQ¿JXUDWLRQSDUDPHWHUVLQVHUWSDVVZRUG
In detail:
• CYCA: Number of consecutive days, without any anti-legionella treatment, after which point a forced treatment is run.
• SEtA: Temperature in the storage tank, above which the anti-legionella treatment is considered as having been carried out (par.112 > par.134).
• tiMA: Minimum continuous time, that the above condition lasts for (par.112 > par.134), after which point the anti-legionella treatment is conside-
red as having been carried out.
• HOUA: Time of day that the forced treatment is carried out.
Forced treatment means switching on the electric resistor, so that par.112 > par.134, for an amount of time equal to par.135.
2EYLRXVO\LIGXULQJQRUPDORSHUDWLRQERWKFRQGLWLRQVUHTXLUHGIRUWKHDQWLOHJLRQHOODWUHDWPHQWDUHIXO¿OOHGWKHQXPEHURIGD\VFRXQWHGZLWKRXWDQ\
treatment starts from zero again.
Menù
label
Par Label Description U.m. Range Correct Address
min max
Default t
SAm1
124 OmP
Start DHW priority period:
The time of day that DHW production has priority over air conditio-
ning
h:
min
00:00 23:59 00:00 16397
125 OFFP
End DHW priority period:
The time of day until DHW production has priority over air conditio-
ning
h:
min
00:00 23:59 23:59 16398
Menù
label
Par Label Description U.m. Range Correct Address
min max
Default t
SAni
133 CYCA
DHW heat treatment start frequency (anti-legionella)
The time interval, in days, that the anti-legionella treatment will be
carried out at. At 0, the function is disabled
day 0 30 0 16405
134 SEtA
DHW heat treatment set point (anti-legionella) °C 50 70 60 16406
135 tiMA
DHW heat treatment start period (anti-legionella) The minimum
continuous amount of time that the water temperature in the storage
tank stays above the set point value
min 1 30 15 16407
136 HOUA
DHW heat treatment start time (anti-legionella)
h:
min
00:00 23:59 02:00 16408
,IWKHVHSDUDPHWHUVDUHQRWFRQ¿JXUHGGRPHVWLFKRWZDWHUSURGXFWLRQZLOODOZD\VKDYHSULRULW\RYHUDLUFRQGLWLRQLQJ
300
Enclosed documentsEN

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RHOSS ELECTA Series and is the answer not in the manual?

RHOSS ELECTA Series Specifications

General IconGeneral
BrandRHOSS
ModelELECTA Series
CategoryHeat Pump
LanguageEnglish

Related product manuals